All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 05D01D12-02E 4th Edition Mar. 01, 2005-00
“SUPER2” function:
The function stabilizes the state of control that
is unstable due to hunting, etc. without
requiring any change in PID constants, when
the load and/or gain varies greatly, or when
there is a difference between the characteris-
tics of temperature zones.
Control Parameters Setting Range
Proportional band = 0.1 to 999.9%
0.0 to 999.9% for heating/cooling control,
0.0% for ON/OFF control
Integral time = 1 to 6000 s, or OFF (manual reset)
Derivative time = 1 to 6000 s, or OFF
Manual reset value = –5.0 to 105.0% of output range
(Functions when integral time is off.)
ON/OFF control hysteresis = 0.0 to 100.0% of PV input
range span (0.1 to 0.5% for heating/cooling
control)
Setpoint rate-of-change setting = OFF, or 0.0 to 100.0%/h
or min of PV input range span
A PV tracking function operates automatically
when the setpoint is changed, the power is
turned on, or the mode is changed from
manual to automatic.
Direct/reverse action:
The output increase/decrease direction can be
defined corresponding to a positive or
negative deviation.
For heating/cooling control, it is fixed; reverse
for the heating-side output, direct for the
cooling- side output.
Anti-reset windup:
When controller output is limited, normal
integration is superseded by an anti-reset
windup computation to suppress over-
integration.
Control output cycle time = 1 to 1000 s for Time-
proportional PID control (The cooling-side
output cycle time is also the same when
heating/cooling control is used.)
Preset output value = –5.0 to 105.0% of output range
Output tracking=Whether the output bump is provided or
not can be selected by changing the PID
control mode.
Output limiter
Upper limit = Lower limit to 105.0% of output
range
Lower limit = –5.0% of output range to upper
limit
Heating/cooling dead band = –100.0 to 50.0% for output
range
Signal Computation Functions
PV input computation:
Bias addition (–100.0 to 100.0% of PV input
range span), and first-order lag filter (time
constant OFF or 1 to 120 s)
Contact input function:
Target setpoint selection, Auto/Man operating
mode switching, key lock parameter show/
hide switching
Target setpoint selection can be done for
either a 2-setpoint or 4-setpoint selection.
• If the 2-setpoint selection is set, Auto/Man
mode switching can be used as well.
• If the 4-setpoint selection is set, Auto/Man
switching and key lock parameter show/hide
switching cannot be used together.
If key lock parameter show/hide switching is used, target
setpoint selection and Auto/Man mode
switching cannot be used.
Alarm Functions
Twenty-four types of alarm functions are provided. The
alarm status is indicated by the alarm lamp on the front
panel. Also, three points among them can be output as relay
contact outputs.
Alarm types:
PV high limit, PV low limit, Deviation high
limit, Deviation low limit, De-energized on
deviation high limit, De-energized on
deviation low limit, Deviation high and low
limits, High and low limits within deviation,
De-energized on PV high limit, De-energized
on PV low limit, SP high limit, SP low limit,
Output high limit, Output low limit, Deviation
high limit for target setpoint, Deviation low
limit for target setpoint, De-energized on
deviation high limit alarm for target setpoint,
De-energized on deviation low limit alarm for
target setpoint, Deviation high and low limits
fot target setpoint, Deviation within high and
low limits for target setpoint, Heater burnout
alarm, Sensor grounding alarm, Fault
diagnostic alarm, and FAIL output.
Alarm output:
3 points. Any three points among the above
alarms can be output as contact outputs . For
heating/cooling control, if cooling-side output
is output as a relay contact, up to two alarm
outputs can be used.
Setting ranges for PV, deviation, setpoint and output alarms:
PV/setpoint alarm:
–100.0 to 100.0% of PV input range
Deviation alarm:
–100.0 to 100.0% of PV input range span
Output alarm:
–5.0 to 105.0% of output range
Alarm hysteresis:
0.0 to 100.0% of PV input range span
Delay timer:
0.00 to 99.59 (minute, second)
An alarm is output when the delay timer
expires after the alarm setpoint is reached.
Setting for each alarm is possible.
Stand-by action:
Stand-by action can be set to make PV/
deviation alarm OFF during start-up or after
SP change until SP reaches the normal region.
Heater burnout alarm (optional):
Two circuits incorporated.
A heater burnout alarm is output if the heater
current consumption is the burnout detection
value or less. This alarm can be used for
Relay ON/OFF control or time-proportional
PID control.
Heater current setting range: 0.0 to 50.0 A
Heater current measuring accuracy: ±5% of span ± 1
digit
Heater current detecting resolution: 0.5 A
Time required until burnout detection is on: 0.13 s
minimum
Burnout sensor model: CTL-6-S-H (URD Co. Ltd.)
Burnout sensor is provided separately.