Sensor grounding alarm:
An alarm is output after detecting a change in
control output. If the moving average * of
control output is out of the setting range
(between the high and low limits of the on/off
rate) in spite of the deviation being within a
fixed range (on/off rate detection band) and
control being in stable condition, the sensor is
judged to be in a grounding condition.
* Moving average refers to the average value for output
values sampled (five times) in every cycle time.
High- and low-limit setting range of on/off rate:
–5.0 to 105.0% of output range
Detection band of on/off rate:
0.0 to 100.0% of PV input range span
Fault diagnostic alarm:
Input burnout, A/D conversion error,
thermocouple RJC error
FAIL output: Abnormality in software or hardware.
When in Fail status, control output, retrans-
mission output and alarm output become 0%
or OFF.
● Display and Operation Functions
PV display: 4-digit digital display for engineering data
Setpoint display:
Various data, such as the setpoint (SP), are
displayed by selection on the 4-digit digital
display.
Status indication:
Alarm indicator lamp
3 lamps: AL1, AL2 and AL3
Setpoint number indicator lamp:
3 lamps: SP2, SP3 and SP4 (not lit when SP1
is selected)
MAN operation mode lamp: MAN (lit in MAN mode)
PV display color changing function “Active Color PV
Display” :
(Factory-set default : Fixed in red mode)
This function automatically changes PV
display color by the action described below.
Green-to-red or red-to-green changing action
is selectable.
Link to alarm 1 mode :
Alarm OFF : green, Alarm ON : red
Setting of Alarm OFF : red, Alarm ON :
green is possible.
Link to alarms 1 and 2 mode :
Alarm OFF : green, Alarm ON : red
Setting of Alarm OFF : red, Alarm ON :
green is possible.
SP deviation mode :
Within the preset SP deviation : green,
Out of the preset SP deviation : red
Setting of within the preset SP deviation :
red, Out of the preset SP deviation : green is
possible.
Deviation band is changeable using a
parameter. The setting of either high limit
deviation or low limit deviation is also
possible.
PV limit mode :
Within the preset PV range : green,
Out of the preset PV range : red
Setting of Within the preset PV range : red,
Out of the preset PV range : green is
possible.
The range (high limit and low limit) is
changeable using a parameter.
Fixed color mode :
PV display color is fixed in green or red.
Operation keys:
쑶 and 쑴 keys:
Increase or decrease setpoints and various
parameters.
SET/ENT key:
Sets setpoint data, calls or selects various
parameters.
A/M key: Switches operation mode (Auto/Man)
SELECT display:
Allows selection and registration of frequently
changed parameters from the operating
parameters during operation.
For example, if the alarm-1 setpoint is
registered in the SELECT display, the setpoint
can easily be displayed during operation.
Security function:
Operation can be inhibited by a password.
Status lamps
Indicate alarm status (AL1, 2, 3), manual operation
(MAN), setpoint No. (SP2, 3, 4) in use.
LED display unit (for PV)
Displays PV and error codes when
errors are detected.
Active color PV display
Indication in green or red color.
LED display unit (for SP)
Displays setpoints (SP), output values,
or setting items/values of parameters.
Operation keys
Increase/decrease the setting data (쑶,쑴).
Select parameter/Enter the setting data (SET/ENT).
Select Auto/Manual operation mode (A/M).
Communication port for light loader
Parameters are set via communication
from a personal computer.